External bypass 2 1/2" BSP
性能特征
Highly efficient industrial chiller
Electronic 2-point temperature control
Integrated water filter
Inlet and outlet water connections in stainless steel
LCD remote control with 5 m cable
Protection level IP 54 (for outdoor installation)
Integrated Ethernet interface
Operates with non flammable liquids (water,water/glycol)
Operation possible via web server
Industrial block pump with high pressure and high flow rate
Integrated phase detector indicates if phase sequence is correct
Meeting the energy efficiency requirements of the EcoDesign directive 2009/125/EC
工作范围
最小工作温度
-10 °C
最大工作温度
35 °C
温度稳定性
0.5 ± K
技术特征(依据 DIN 12876)
工作温度范围
-10 ... 35 °C
环境温度范围
-15 ... 50 °C
温度稳定性
0.5 ± K
最大灌注容积
125 L
最大输送压力
5,3 bar (50 Hz), 7,5 bar (60 Hz)
泵最大输送流量(压力)
367 L/min (50 Hz); 450 L/min (60 Hz)
泵额定输送流量
300 L/min
连接螺纹(内部)输入/输出
Rp 2 1/2
尺寸(宽x深x高)
1256 x 1706 x 1905 mm
重量
700 kg
声压级
69.3 dB(A)
电源供应
400 V; 3/PE; 50 Hz & 460 V; 3/PE; 60 Hz
电源插头
---
Temperatur | Kälteleistung 50 Hz | Kälteleistung 60 Hz |
---|---|---|
25 °C | 124,7 kW | 124,7 kW |
20 °C | 121,4 kW | 121,4 kW |
15 °C | 110,2 kW | 110,2 kW |
10 °C | 95,3 kW | 95,3 kW |
5 °C | 81,7 kW | 81,7 kW |
0 °C | 68,3 kW | 68,3 kW |
-5 °C | 57,5 kW | 57,5 kW |
-10 °C | 47,8 kW | 47,8 kW |