External Bypass
性能特征
Highly efficient industrial chiller
Electronic 2-point temperature control
Integrated water filter
Operates with non flammable liquids (water,water/glycol)
Water cooled version (W)
LCD remote control with 5 m cable
Protection level IP 54 (for outdoor installation)
Integrated Ethernet interface
Meeting the energy efficiency requirements of the EcoDesign directive 2009/125/EC
Reinforced pump in stainless steel
Operation possible via web server
Industrial block pump with high pressure and high flow rate
Inlet and outlet water connections in stainless steel
Condenser cooling Water
工作范围
最小工作温度
-10 °C
最大工作温度
35 °C
温度稳定性
0.5 ± K
技术特征(依据 DIN 12876)
工作温度范围
-10 ... 35 °C
环境温度范围
-15 ... 50 °C
温度稳定性
0.5 ± K
最大灌注容积
35 L
最大输送压力
6,8 bar
泵最大输送流量(压力)
106 L/min
泵额定输送流量
43.8 L/min
连接螺纹(内部)输入/输出
Rp 1
Water Cooling Connection Thread Inside
Rp 1
尺寸(宽x深x高)
720 x 910 x 1250 mm
重量
175 kg
声压级
64.7 dB(A)
电源供应
400 V; 3/PE; 50 Hz
电源插头
---
Temperatur | Kälteleistung 50 Hz |
---|---|
25 °C | 22,4 kW |
20 °C | 20,3 kW |
15 °C | 18,4 kW |
10 °C | 15,8 kW |
5 °C | 13,4 kW |
0 °C | 11,1 kW |
-5 °C | 9,3 kW |
-10 °C | 7,6 kW |