External Bypass
性能特征
Highly efficient industrial chiller
Electronic 2-point temperature control
Integrated water filter
Operates with non flammable liquids (water,water/glycol)
LCD remote control with 5 m cable
Protection level IP 54 (for outdoor installation)
Integrated Ethernet interface
Meeting the energy efficiency requirements of the EcoDesign directive 2009/125/EC
Operation possible via web server
Industrial block pump with high pressure and high flow rate
Inlet and outlet water connections in stainless steel
Condenser cooling Air
工作范围
最小工作温度
-10 °C
最大工作温度
35 °C
温度稳定性
0.5 ± K
技术特征(依据 DIN 12876)
工作温度范围
-10 ... 35 °C
环境温度范围
-15 ... 50 °C
温度稳定性
0.5 ± K
最大灌注容积
210 L
最大输送压力
5,0 bar (50 Hz), 7,2 bar (60 Hz)
泵最大输送流量(压力)
250 L/min (50 Hz); 300 L/min (60 Hz)
泵额定输送流量
196 L/min
连接螺纹(内部)输入/输出
Rp 1 1/2
尺寸(宽x深x高)
1040 x 1435 x 1890 mm
重量
427 kg
声压级
69.5 dB(A)
电源供应
400 V; 3/PE; 50 Hz & 460 V; 3/PE; 60 Hz
电源插头
---
Temperatur | Kälteleistung 50 Hz | Kälteleistung 60 Hz |
---|---|---|
25 °C | 87,5 kW | 87,5 kW |
20 °C | 85,2 kW | 85,2 kW |
15 °C | 77,4 kW | 77,4 kW |
10 °C | 66,9 kW | 66,9 kW |
5 °C | 57,3 kW | 57,3 kW |
0 °C | 47,8 kW | 47,8 kW |
-5 °C | 40,1 kW | 40,1 kW |
-10 °C | 33,3 kW | 33,3 kW |